3000 University Dr
Spaces
About This Property
Building description
Ample power from dual primary feeds.
Building highlights
ADDRESS
3000 UNIVERSITY, AUBURN HILLS, 48326
BUILDING
Four story, single-tenant office building totaling 445,234 square feet Originally constructed in 1988 and most recently renovated in 2018.
LAND
34.74 AC; PARCEL 14-14-476-003
PARKING
1552 surface parking
COUNTY
Oakland County
ZONING
T&R Technology & Research; advanced engineering, R&D/lab, AI inference, secure technology, enterprise compute, prototype development, and hybrid R&D / powered shell
ELECTRICAL
Core Infrastructure, additions made to support expansions. Two Independent 13.2 kV DTE feeders located in shared underground duct bank. Multiple utility-owned switches at site perimeter.
ELECTRICAL CAPACITY
Total Electrical Capacity 9MW, Usable Capacity 7.2 MW (80% Load Factor). Immediate Available Capacity 2.5 MW. Utility request submitted for additional capacity.
MEDIUM VOLTAGE (MV) SWITCHGEAR
DTE-owned 13.2 kV main switchgear. Main-Tie- Main configuration. Automatic transfer scheme (open transition).
SWITCHGEAR RATINGS
• 13.5kV, 95BIL, 600A, 25kA SCIR (RMS)
• Main Switches – Max Fuse Rating 400E
• Tie Switch – Rated 600A
• Feeder Switches – Max Fuse 400E
• Sub G Feeder Switch – Max Fuse 200E
SUBSTATIONS
6 Substations. Five (5) @ 1.5-2 MVA (Dry Type AA/FA) ; One (1) @ 2 MVA (Oil Filled OA/FA) ; Voltage 13.2 kV 480/277V.
COOLING SYSTEMS
CENTRAL SYSTEM: Single cooling tower (Baltimore Aircoil/Model #3654 2 MC~1988), 650 distributed heat pumps. LAB SYSTEM: Rooftop units (McQuay 40 Ton) installed 2008 and (McQuay 12 Ton) installed 2012. Fully sprinkled building.
GAS
2’ Gas service line connected to 4” medium-pressure main